Completely Sealed Distribution Transformer
Completely Sealed Distribution Transformer contains
oil tank, which is completely isolated from air. The elasticity feature
of the oil tank compensates the volume transformation of oil tank, the
moisture and oxygen cannot enter the tank. This can slow down the aging
of insulating materials. This improves operation reliability of the
product.
Features
1. The oil inside transformer isolates from air and ensure the
transformer can be used continuously for 20 years without any special process. There are no oil storage tank and protection devices.
2. The transformer applies vacuum oiling in the vacuum oil filling plant equipped at JAYBEE to achieve sealed effect.
Application
City Electric Network, Petrifaction, Metallurgy and other occasions with heavy humidity and in convenient maintenance.
Technical Specification
Capacity
(kVA)
|
Voltage Schedule
|
Vector
Group
|
Consumption
|
Short Circuit
Impedance (%)
|
No Load
Current (%)
|
Outline Dimension
mm (+-10%)
|
Weight
kg (+-10%)
|
Gauging
Distance (mm)
|
HV (kV)
|
LV (kV)
|
No Load (W)
|
Load (W)
|
Length
|
Width
|
Height
|
Oil
|
Total
|
20
|
|
|
|
110
|
530
|
|
2.3
|
730
|
720
|
1015
|
90
|
290
|
400x450
|
30
|
|
|
|
130
|
600
|
|
2.1
|
1050
|
670
|
1030
|
95
|
370
|
400x450
|
50
|
|
|
|
170
|
870
|
|
2
|
1100
|
690
|
1120
|
110
|
440
|
400x450
|
63
|
6
|
|
|
200
|
1040
|
|
1.9
|
1120
|
670
|
1120
|
110
|
480
|
400x450
|
80
|
6.3
|
|
|
240
|
1250
|
|
1.8
|
1145
|
675
|
1190
|
115
|
535
|
400x450
|
100
|
11
|
|
|
290
|
1500
|
|
1.6
|
1165
|
695
|
1210
|
120
|
620
|
400x450
|
125
|
+-2
|
|
D, yn11
|
340
|
1800
|
4
|
1.5
|
1195
|
700
|
1235
|
130
|
670
|
400x450
|
160
|
x 2.5%
|
0.433
|
Y, yn0
|
400
|
2200
|
|
1.4
|
1250
|
725
|
1280
|
160
|
770
|
550x550
|
200
|
|
|
|
480
|
2600
|
|
1.3
|
1275
|
730
|
1305
|
175
|
925
|
550x550
|
250
|
|
|
|
560
|
3050
|
|
1.2
|
1325
|
765
|
1370
|
220
|
1150
|
550x650
|
315
|
|
|
|
670
|
3650
|
|
1.1
|
1365
|
775
|
1390
|
230
|
1290
|
550x650
|
400
|
|
|
|
800
|
4300
|
|
1
|
1455
|
825
|
1475
|
270
|
1530
|
550x660
|
500
|
5%
|
|
|
960
|
5100
|
|
1
|
1440
|
790
|
1530
|
295
|
1675
|
660x660
|
630
|
|
|
|
1200
|
6200
|
|
0.9
|
1600
|
875
|
1580
|
400
|
2260
|
660x850
|
800
|
|
|
|
1400
|
7500
|
4.5
|
0.8
|
1720
|
985
|
1760
|
425
|
2665
|
820x850
|
1000
|
|
|
|
1700
|
10300
|
|
0.7
|
1850
|
1180
|
1710
|
510
|
2970
|
820x850
|
1250
|
|
|
|
1950
|
12800
|
|
0.6
|
1970
|
1190
|
1775
|
545
|
3440
|
820x850
|
1600
|
|
|
|
2400
|
14500
|
|
0.6
|
2080
|
1130
|
1840
|
560
|
3840
|
820x900
|
2000
|
|
|
|
2830
|
17140
|
|
0.5
|
2080
|
1320
|
2280
|
1170
|
5800
|
1070x1070
|
2500
|
|
|
|
3350
|
20260
|
|
0.5
|
2400
|
2100
|
2350
|
1280
|
6500
|
1070x1070
|
Note: Dimensions and weights etc. given above are just indicative. We
reserve our right for constant improvement / modifications.Standard Fittings
- Conservator
- Silicagel Breather
- Off Circuit Top Changer
- Oil Level Gauge
- HV Bushing
- LV Bushing
- Air Release Plug
- Lifting Lugs
- Rating & Diagram Plates
- Radiators
- Base Channel with Rollers
- Earthing Terminals
- Explosion Vent.
Note: Transformers with other Voltage Ratio, Vector
Group, Terminal arrangement can be supplied as per the customers
requirement. Fittings like Cable end box, Gas operated relay, MOG, Marshalling box can be provided as per the requirement.
Transformers with lower No Load Losses and Load Losses can also be supplied.
|